2-Way Piloted Diaphragm
General Service Solenoid Valves

Thermo-Polymer Alloy Bodies » 3/8" - 1/2" NPT

General Information:
The Industrial Line of Thermo-Polymer Ally valves provides the highest reliability even under the most demanding of applications.  These valves are well suited for use with salt water, ozonated water systems, various organic solvents, potable drinking water systems and high compatibility with various automotive media.  their high tensile strength also makes them a good replacement for brass or the more expensive stainless steel valves.  the I81 series valves do not require a minimum operating pressure, which allows them to operate from a "zero" inlet pressure to the maximum operating pressure differential (MOPD).  These valves also provide a bubble-tight shutoff.

Mounting Position:
Any Position (best if vertical and upright)

Actuation Response Time:
30-50 milliseconds is typical

Electrical Specifications:
Standard Voltages:
VAC 24/60, 110/50-120/60, 220/50-240/60, 440/50-480/60
VDC:12, 24, 48, 120

 

Coil Rating:
Continuous duty totally encapsulated
Class F Rated 155°C; 311°F

Voltage Tolerances:
+10%, -15% of applicable voltage

Standard Lead Length: 24"

Nominal Ambient Temperature Ranges:
-40°C to 65.5°C; -40°F to 150°F

Enclosure Options:
NEMA I (std)- Metal Housing

NEMA IV - Watertight Housing

NEMA VII - Explosion-Proof Housing
(All options come with 1/2" FPT Conduit Connection)


DIN -
Form "A" Connection

Operating Modes Available:
Normally Closed - Closed when de-energized, open when energized
Normally Open - Open when de-energized, closed when energized

Valve Parts in Contact with Media:
Body - Noryl GTX830

Internals -
S/S T316

Core Tube -
S/S T305

Plunger and Core Plug -
S/S T430F

Shading Ring (AC unites only) -
Copper (std); Silver (special order only)

Springs -
S/S T302

Seals -
Nitrile (std on Brass valves); 

Diaphragm - Nylon Reinforced Nitrile

Options:
• Seals: EPDM, Viton, Teflon
• Class H Rated Coil
• Latching Solenoids

Other voltages, coil constructions, lead lengths and materials are available to meet special requirements.

  Technical Data, Mounting Holes, Flow Patterns


AC Valve Specifications Solenoid Specification
Add one code from each
Port Size (in) Orifice Size (in) Cv Factor

Operating Press

Max. Operating Temp

Coil Wattage

 

Base Part Number
Voltage Enclosure/ Termination
Min. AC
Air/Gas/Water
Max. (MOPD)
AC
Light Oil
Max. (MOPD)
(psi) (bar) (psi) (bar) (psi) (bar) °F °C

Normally Closed (Closed When De-Energized)

AC
05 -
 24-50/60

10 -
 110/50-
 120/60

23 -
 220/50-
 240/60

40 -
 440/50-
 480/60

Std
D1 -
 NEMA I

Optional
LK
-
 Din "A"

D4
 NEMA IV

D7 -
 NEMA VII

3/8 5/8 3.3 0 0 140 9.8 90 6.3 180 82.2 10 I8105X-402CN-F4
5/8 3.3 4 .28 150 10.5 150 10.5 180 82.2 10 I2105X-402CN-F4
1/2 5/8 4.1 0 0 140 9.8 90 6.3 180 82.2 10 I8106X-402CN-F4
5/8 4.1 4 .28 150 0.5 150 10.5 180 82.2 10 I2106X-402CN-F4

Normally Open (Open When De-Energized)

3/8 5/8 3.3 0 0 180 12.6 180 12.6 180 82.2 11 I8105X-402ON-F5
5/8 3.3 4 .28 180 12.6 180 12.6 180 82.2 11 I2105X-402ON-F5
1/2 58 4.1 0 0 180 12.6 180 12.6 180 82.2 11 I8106X-402ON-F5
5/8 4.1 4 .28 180 12.6 180 12.6 180 82.2 11 I2106X-402ON-F5

 

DC Valve Specifications Solenoid Specification
Add one code from each
Port Size (in) Orifice Size (in) Cv Factor

Operating Press

Max. Operating Temp

Coil Wattage

 

Base Part Number
Voltage Enclosure/ Termination
Min. DC
Air/Gas/Water
Max. (MOPD)
DC
Light Oil
Max. (MOPD)
(psi) (bar) (psi) (bar) (psi) (bar) °F °C

Normally Closed (Closed When De-Energized)

DC
72 -
 12 VDC

75-
 24 VDC

Std
D1 -
 NEMA I

Optional
LK
-
 Din "A"

D4
 NEMA IV

D7 -
 NEMA VII

3/8 5/8 3.3 0 0 90 6.3 70 4.9 180 82.2 10 I8105X-402CN-F4
5/8 3.3 4 .28 150 10.5 100 7.0 180 82.2 10 I2105X-402CN-F4
1/2 5/8 4.1 0 0 90 6.3 70 4.9 180 82.2 10 I8106X-402CN-F4
5/8 4.1 4 .28 150 10.5 100 7.0 180 82.2 10 I2106X-402CN-F4

Normally Open (Open When De-Energized)

3/8 5/8 3.3 0 0 125 8.7 125 8.7 180 82.2 10 I8105X-402ON-F4
5/8 3.3 4 .28 140 9.8 125 8.7 180 82.2 10 I2105X-402ON-F4
1/2 58 4.1 0 0 125 8.7 125 8.7 180 82.2 10 I8106X-402ON-F4
5/8 4.1 4 .28 140 9.8 125 8.7 180 82.2 10 I2106X-402ON-F4

 

    
Operational Sequence / Flow Patterns:

2-Way Normally Closed

2-Way Normally Open

   
Wattage Rating / Power Consumption:
AC DC
Wattage 60 Hz 50 Hz Wattage
VA
Inrush
VA 
Holding
VA
Inrush
VA 
Holding

Normally Closed

9

10

10 30 13 37 18

Normally Open

11 (I21) 51 16 56 23
11 (I81) 37 16 43 23
     AC
     Inrush Amps = Volt-Amp Inrush / Voltage
     Holding Amps = volt-amp Holding / Voltage

     DC
     Since DC valves have no Inrush current, the amp rating can 
     be determined:
     Amps = Watts (DC) / Voltage

   
Valve Dimensions:
Pipe
Size
A Normally Closed
B
Normally Open 
B
C Weight
3/8" 2.76 3.9 4.33 2.2 .80
1/2" 2.76 3.9 4.33 2.2 .80
     
Latching Valve 2-Wire Circuit:
Lead Wires:              Red (+)  is for Latching; 
                                 Black (-) is common

Current Pulse:          A 12 VDC 30-50 ms pulse is 
                                 required to latch actuator in the 
                                 open or closed position.  A 
                                 pulse longer than 50 ms may 
                                 cause the armature to re-actuate.