Operational Sequence / Flow Patterns:

2-Way Normally Closed

2-Way Normally Open

           
Wattage Rating / Power Consumption:
AC DC
  60 Hz 50 Hz  
Wattage VA
Inrush
VA
 Holding
VA
Inrush
VA
 Holding
Wattage
Normally Closed 9

10

8 22 11 26 14
10 30 13 37 18
Normally Open
8 30 14 35 19
11 37 16 43 23
     AC
     Inrush Amps = Volt-Amp Inrush / Voltage
     Holding Amps = volt-amp Holding / Voltage

     DC
     Since DC valves have no Inrush current, the amp rating can 
     be determined:
     Amps = Watts (DC) / Voltage

      
Valve Dimensions:
Pipe Size A Normally Closed
B
Normally Open
B
C Weight
(lbs.)
3/8" 2.76 3.90 4.33 2.20 1.8
1/2" 2.76 3.90 4.33 2.20 1.8
3/4" 2.76 4.09 4.53 2.20 1.8
1" 3.62 4.77 5.08 3.23 3.8
1-1/4" 4.33 5.39 5.71 3.62 5.8
1-1/2" 4.33 5.39 5.71 3.62 5.8
2" 5.51 5.95 6.26 3.62 8.9
   
Latching Valve 2-Wire Circuit:
Lead Wires:              Red (+)  is for Latching; 
                                 Black (-) is common

Current Pulse:          A 12 VDC 30-50 ms pulse is 
                                 required to latch actuator in the 
                                 open or closed position.  A 
                                 pulse longer than 50 ms may 
                                 cause the armature to re-actuate.