| Operational Sequence /
Flow Patterns: |
|
|
2-Way Normally
Closed |
2-Way Normally
Open |
 |
 |
 |
 |
| |
| Wattage Rating
/ Power Consumption: |
|
| AC |
DC |
| |
60 Hz |
50 Hz |
|
| Wattage |
VA Inrush |
VA Holding |
VA Inrush |
VA Holding |
Wattage |
| Normally Closed |
10
22.5 |
| 10 |
30 |
13 |
37 |
18 |
| 17.5 |
130 |
22 |
150 |
27 |
| Normally
Open |
| 11 |
37 |
16 |
43 |
23 |
| 18.5 |
130 |
22 |
160 |
28 | |
AC Inrush Amps = Volt-Amp Inrush /
Voltage Holding Amps = volt-amp Holding
/ Voltage
DC Since DC valves have no Inrush
current, the amp rating can be
determined: Amps = Watts (DC) /
Voltage |
| |
| Valve
Dimensions: |
|
 |
| Pipe Size |
A |
Normally Closed B |
Normally Open B |
C |
Weight (lbs.) |
| 3/8" |
2.76 |
3.9 |
4.33 |
2.20 |
2.0 |
| 1/2" |
2.76 |
3.9 |
4.33 |
2.20 |
2.0 |
| 3/4" |
2.76 |
4.09 |
4.53 |
2.20 |
2.2 |
| 1" |
3.62 |
6.57 |
7.44 |
3.23 |
5.1 |
| 1-1/4" |
4.33 |
7.28 |
8.15 |
3.62 |
6.7 |
| 1-1/2" |
4.33 |
7.28 |
8.15 |
3.62 |
6.7 |
| 2" |
5.51 |
7.80 |
8.66 |
3.62 |
9.1 | |
| |
|
| Latching Valve 2-Wire
Circuit: |
|
 |
Lead
Wires:
Red (+) is for
Latching; Black
(-) is common
Current
Pulse:
A 12 VDC 30-50 ms pulse
is required
to latch actuator in
the open
or closed position.
A pulse
longer than 50 ms
may cause
the armature to re-actuate. |
| |
|