Operational Sequence / Flow Patterns:

2-Way Normally Closed

2-Way Normally Open

           
Wattage Rating / Power Consumption:
AC DC
  60 Hz 50 Hz  
Wattage VA
Inrush
VA
 Holding
VA
Inrush
VA
 Holding
Wattage
Normally Closed 10

22.5

10 30 13 37 18
17.5 130 22 150 27
Normally Open
11 37 16 43 23
18.5 130 22 160 28
     AC
     Inrush Amps = Volt-Amp Inrush / Voltage
     Holding Amps = volt-amp Holding / Voltage

     DC
     Since DC valves have no Inrush current, the amp rating can 
     be determined:
     Amps = Watts (DC) / Voltage

      
Valve Dimensions:
Pipe Size A Normally Closed
B
Normally Open
B
C Weight
(lbs.)
3/8" 2.76 3.9 4.33 2.20 2.0
1/2" 2.76 3.9 4.33 2.20 2.0
3/4" 2.76 4.09 4.53 2.20 2.2
1" 3.62 6.57 7.44 3.23 5.1
1-1/4" 4.33 7.28 8.15 3.62 6.7
1-1/2" 4.33 7.28 8.15 3.62 6.7
2" 5.51 7.80 8.66 3.62 9.1
   
Latching Valve 2-Wire Circuit:
Lead Wires:              Red (+)  is for Latching; 
                                 Black (-) is common

Current Pulse:          A 12 VDC 30-50 ms pulse is 
                                 required to latch actuator in the 
                                 open or closed position.  A 
                                 pulse longer than 50 ms may 
                                 cause the armature to re-actuate.

   