3-Way Piloted Diaphragm
General Service Solenoid Valves

Brass Bodies » 3/8" - 1/2" NPT

General Information:
The Industrial Line of valves provides the highest reliability even under the most demanding of applications.  The I31 3-way series piloted diaphragm valves do require a minimum operating pressure, which allows them to operate properly but offer a higher flow (Cv).  These valves also provide a bubble-tight shutoff and work well with gasses, fluids, light oils and other clean flowing media.

Mounting Position:
Any Position (best if vertical and upright)

Actuation Response Time:
50-75 milliseconds is typical

Electrical Specifications:
Standard Voltages:
VAC 24/60, 110/50-120/60, 220/50-240/60, 440/50-480/60
VDC:12, 24, 48, 120

Coil Rating:
Continuous duty totally encapsulated
Class F Rated 155°C; 311°F

Voltage Tolerances:
+10%, -15% of applicable voltage

Standard Lead Length: 24"

Nominal Ambient Temperature Ranges:
-40°C to 65.5°C; -40°F to 150°F

Enclosure Options:
NEMA I (std)- Metal Housing

NEMA IV - Watertight Housing

NEMA VII - Explosion-Proof Housing
(All options come with 1/2" FPT Conduit Connection)


DIN -
Form "A" Connection

Operating Modes Available:
Normally Closed - Closed when de-energized, open when energized
Normally Open - Open when de-energized, closed when energized

Valve Parts in Contact with Media:
Body - Brass

Poppet Fork -
Polyacetal

Cartridge -
Polyacetal

Core Tube -
S/S T305

Plunger and Core Plug -
S/S T430F

Shading Ring (AC unites only) -
Copper (std); Silver (special order only)

Springs -
S/S T302

Seals -
Nitrile  

Diaphragm - Nylon Reinforced Nitrile

Options:
• Seals: EPDM, Viton
• Class H Rated Coil
• Mounting Bracket

Other voltages, coil constructions, lead lengths and materials are available to meet special requirements.

  Technical Data, Mounting Holes, Flow Patterns


Valve Specifications Solenoid Specification
Add one code from each
Port Size (in) Orifice Size (in) Cv Factor

Operating Press

Max. Operating Temp

Coil Wattage

 

Base Part Number
Voltage Enclosure/ Termination
Min. AC
Air/Gas/Water
Max. (MOPD)
DC
Light Oil
Max. (MOPD)
(psi) (bar) (psi) (bar) (psi) (bar) °F °C

Normally Closed (Closed When De-Energized)

AC
05 -
 24-50/60

10 -
 110/50-
 120/60

23 -
 220/50-
 240/60

40 -
 440/50-
 480/60

DC
72 -
 12 VDC

75-
 24 VDC

Std
D1 -
 NEMA I

Optional
LK
-
 Din "A"

D4
 NEMA IV

D7 -
 NEMA VII

3/8 5/8 3.3 7 .5 150 10.5 150 10.5 180 82.2 10 I3105F-402CN-F4
1/2 5/8 4.4 7 .5 150 10.5 150 10.5 180 82.2 10 I3106F-402CN-F4

Normally Open (Open When De-Energized)

3/8 5/8 3.3 7 .5 150 10.5 150 10.5 180 82.2 10 I3105F-402ON-F4
1/2 58 4.4 7 .5 150 10.5 150 10.5 180 82.2 10 I3106F-402ON-F4

 

    
Operational Sequence / Flow Patterns:

2-Way Normally Closed

2-Way Normally Open

   
Wattage Rating / Power Consumption:
AC DC
Wattage 60 Hz 50 Hz Wattage
VA
Inrush
VA 
Holding
VA
Inrush
VA 
Holding

Normally Closed / Normally Open

10

10 30 13 37 18
     AC
     Inrush Amps = Volt-Amp Inrush / Voltage
     Holding Amps = volt-amp Holding / Voltage

     DC
     Since DC valves have no Inrush current, the amp rating can 
     be determined:
     Amps = Watts (DC) / Voltage

   
Valve Dimensions:
Weight (lbs.) 3.50
(Dimension shown are with optional mounting bracket)
     