PRESSURE DROP - The graph above
shows the expected pressure loss per foot of bed depth as a function of flow
rate at various temperatures.Features
- Highest operating capacity of any nitrate selective
resin.
- Uniform particle size.
- Low pressure drop, superior kinetics.
- Superior, physical stability.
- Low sulfate selectivity and high operating capacity.
| Physical Properties |
Polymer Structure
Functional Group
Ionic Form, as shipped
Physical Form
Screen Size Distribution
+16 mesh (U.S. Std.)
-40 mesh (U.S. Std.)
-50 mesh (U.S. Std.)
pH Range
Sphericity
Water Retention
Chloride Form
Solubility
Approximate Shipping Weight
Chloride Form
Swelling Ca+2 or Na+ to H+
Total Capacity
Chloride Form |
Styrene with DVB
R-N-R3+X-
Chloride
Tough, spherical beads
16 to 45 nominal
<5 percent
<2 percent
<1 percent
0 to 14
95+ percent
52 to 60 percent
Insoluble
41 lbs/ft3
12 percent
0.85 meq/ml min |
|
ProSelect Nitrate represents one
of the newest advancements in ion exchange technology. This is one of the first
resins to be preferential to nitrates over sulfates and other ions in the
water. It removes and than holds onto nitrates so they arent dumped back
into the water supply. This makes ProSelect Nitrate the perfect choice to solve
nitrate contamination problems in well water applications.
CAUTION: DO NOT MIX ION EXCHANGE
RESINS WITH STRONG OXIDIZING AGENTS. Nitric acid and other strong
oxidizing agents can cause explosive reactions when mixed with organic
materials such as ion exchange resins.
Note: These suggestions and data
are based on information we believe to be reliable. However, we do not make any
guarantee or warranty. We caution against using these products in any unsafe
manner or in violation of any patents. Further, we assume no liability for the
consequences of any such actions.
| Suggested
Operating Conditions |
Maximum Temperature
Chloride Form
|
170°F |
| Minimum Bed Depth |
24 inches |
Backwash Rate
50% Bed Expansion @
60ºF |
1.9 gpm/ft2
|
| Regenerant |
10% NaCl
& 0.5% NaOH mixture |
| Regenerate Flow Rate |
0.2 to 0.5 gpm/ft3 |
| Regenerate Contact Time
|
At least 60 minutes |
| Regenerate Level |
10 to 15 lbs/ft3 plus
proptional amount of NaOH |
| Displacement Rinse Rate
|
Same as Regenerate Flow
Rate |
| Displacement Rinse Volume
|
10 to 15 gal/ft3 |
| Fast Rinse Rate |
Same as Service Flow
Rate |
| Fast Rinse Volume |
35 to 60 gal/ft3 |
| Service Flow Rate |
2 to 4 gpm/ft3 |
|